walk-in cooler refrigeration failure and maintenance method (5)

refrigeration failure and maintenance method (5)
Poor refrigeration and corrosion-like failure phenomenon somewhere in the evaporator: Poor refrigeration, corrosion-like somewhere in the evaporator pipe. Fault analysis: 60% is the leakage of the corrosive refrigeration pipeline, followed by the leakage of other refrigeration pipelines, and the compressor performance is poor in some cases. Troubleshooting: unplug the power plug, open the compressor process nozzle to vent and observe the refrigeration discharge, secondly, the total pressure of the system is 0.8MPa. Apply soapy water to the corroded part of the evaporator to check for leakage. There may be three situations as follows appear.
①
walk-in cooler The amount of refrigerant discharged is small, and the evaporator is corroded with bubbles. This means that the corroded area is called for leaks, the nitrogen in the system is released, and the corroded area and the surrounding area are polished 0.5 cm with sawtooth, and an appropriate amount of AB double-tube glue is mixed evenly and wiped on the corroded area for 0.5 hours after curing. once.
②The amount of refrigerant discharged is small, and there are no bubbles in the corroded area of the evaporator. This shows that the system does have leaks, but the leaks are not where the evaporator is corroded. The soapy water should be applied to the welds of the exposed pipelines, where there are air bubbles, the leaks are located, and then the high-pressure pipeline and the low-pressure pipeline should be pressured to check for leakage. The leaking point is repaired on the exposed tube, the leaking point is thrown away in the anti-dew tube, and the leaking point is in the evaporator and cannot be disassembled, then the evaporator is embedded in the
walk-in cooler.
③ The amount of refrigerant discharged is large. Open the outlet of the compressor by welding, plug in the power supply to make the compressor run, and press the outlet of the exhaust pipe with your thumb. If you can hold it down, the compressor has poor exhaust performance. Replace the compressor of the same model. After the refrigeration system is repaired, blow through the system, replace the filter drier, evacuate again, add refrigerant, test the machine, and seal the system.
the cooling of the intercooler is poor and the fan does not run. Trouble phenomenon: poor cooling, the fan does not run, the thermostat adjustment knob is placed in the middle position, open the freezer door, use your hand Press the fan switch button, it still does not work. Failure analysis: The fan does not run and the evaporator cooling capacity is not good enough, which makes the
walk-in cooler appear as poor cooling. There may be a problem with the fan motor circuit, or the fan blade may be stuck in ice. Troubleshooting: Remove the air duct grid on the back of the freezer compartment, observe the fan blades, and measure the windDetermine the fault range by fan motor terminal resistance and voltage.
① The fan blades are jammed by ice, rotate the defrost timer to the defrost position (turn to click and make a sound). If the
walk-in cooler defrosts but the fan still does not run after the defrost is completed, it means that the fault lies in the fan motor circuit. Press and the fan blades rotate flexibly. Check: If it does not defrost, the fault is in the defrost circuit. Check in turn Temperature fuse, defrost heater (normal resistance value is about 350Q), regulating thermostat (water ingress, corrosion is damaged), defrost timer (coil resistance value is about 8kQ, the three contact terminals should rotate with it The adjustment of the button is switched on and off alternately).
②The fan blades rotate flexibly, indicating that the fault lies in the fan motor circuit. Measure the resistance between the two terminals of the fan motor. The normal value should be 330Q-390Q. If it is too large or small, it will be damaged. Secondly, measure the voltage between the two terminals of the fan motor. If there is AC 220V voltage, replace or repair the fan motor: if there is no AC 220V voltage, check the fan switch. [Note] The fan generally has insurance, and the insurance specifications are generally 250V/ 10A, and the melting temperature is 142℃.
the above articles are from refrigerated showcase walk-in cooler, walk-in cooler prices, please visit: www .ihdjx.com
free order hotline: +86 18019567573
keywords:
Ranking of similar articles
- walk-in cooler disassembly and maintenance method
- Dragon fruit reveals ark makes pitaya ornamental fruit
- May 2011 refrigerated showcase Qingyuan Tour
- Represent the frozen watermelon fruit for storage
- Refrigerated showcase major sales walk - cooler in class
- 2012 take care of the old man from the supermarket refrigerated showcase
- Refrigerated showcase walk - in cooler energy-saving progresses steadily
- Refrigerated showcase walk - in cooler cleaner which aspects should be paid attention to
- refrigerated showcase Tip: Which fruits are not suitable for placing in the fruit refrigerated showcase
- Small convenience store owner should show how to choose the convenience stores ltd. refrigeration
- 2013 refrigerated showcase ltd. refrigeration lunar New Year holiday notice
- Air-conditioner noise?
- Commercial refrigeration evaporator embedment and production (6)
- The structure and working principle of computer-based supermarket refrigerated showcase
- The rapid growth of the supermarket walk-in cooler market in refrigeration equipment
- display cases Refrigeration failures and maintenance methods (9)
- walk-in cooler refrigeration failure and maintenance method (5)
- Walk-in cooler secondary failure unit refrigeration difference analysis (2)
- The general principle of design and layout of display cooler refrigeration system
- The air-conditioner doesn't automatically melt frost failure analysis
Latest news articles
- May 2011 refrigerated showcase Qingyuan Tour
- refrigerated showcase Refrigeration Equipment Co., Ltd. growth process
- Refrigerated showcase major sales walk - cooler in class
- Refrigerated showcase display cooler written commercial display cooler legend
- Refrigerated showcase walk - in cooler energy-saving progresses steadily
- 2012 take care of the old man from the supermarket refrigerated showcase
- refrigerated showcase Tip: Which fruits are not suitable for placing in the fruit refrigerated showcase
- Dragon fruit reveals ark makes pitaya ornamental fruit
- Watermelon fresh-keeping refrigerator can better preserve the nutrients of watermelon
- Represent the frozen watermelon fruit for storage
- Hairy crabs freezer frozen taste more fresh
- How hairy crabs fresh refrigerated showcase display cooler tell you
- Large supermarket display ark how to choose the right goods
- Small convenience store owner should show how to choose the convenience stores ltd. refrigeration
- Refrigerated showcase ltd. refrigeration has been a leader in innovation and energy saving
- In September 2012, refrigerated showcase west chung
- Refrigerated showcase walk - in cooler cleaner which aspects should be paid attention to
- Correctly use refrigerated showcase supermarket refrigerated showcase the matters needing attention
- , a refrigerated display showcase meat cooler features of the product
- Refrigerated showcase walk - in the cooler is icy