The freezer compressor is running without cooling failure (3)

The freezer compressor is running without cooling failure (3)
No refrigeration, the compressor rotates and there is no abnormal appearance: no refrigeration, the compressor operates normally, the exposed refrigeration pipeline has no oil stains, and the freezing side of the middle door frame has no rust. Failure analysis: Most of the anti-exposure pipes leak or the compressor does not exhaust, and the other refrigeration pipes are leaky. Troubleshooting: Plug in the freezer power supply and run the compressor for 10 minutes to 20 minutes. When it continues to run, open the process nozzle of the compressor and observe the suction and exhaust conditions.
① A large amount of gas is discharged from the process nozzle, indicating that the amount of refrigerant in the system is acceptable, but the compressor does not discharge. Because the compressor process nozzle is of low pressure, it has a suction function instead of a discharge function. Unplug the power supply, weld the compressor exhaust pipe port, and then plug in the power supply to make the compressor run. Press the exhaust pipe port with your fingers. If it is easy to block, it further indicates that the compressor is not exhausted or the exhaust is poor. Replace the compressor of the same model.
②No gas is discharged from the process nozzle, and it feels to suck inward, indicating that the compressor exhaust pipe has a normal suction and exhaust function, that is, the compressor is normal. The anti-dew pipe should be pressured to 1.2MPa first to check for leaks, and then other refrigeration pipes should be pressured to check for leaks as usual. The anti-dew pipe is not used. Connect the condenser and the compressor exhaust pipe: If the condenser and other high-pressure pipelines are leaking, use soapy water to find the leak and repair the welding: If the evaporator leaks, the detachable model For repair welding, the non-removable model is equipped with an evaporator. After the refrigeration system is repaired, perform a blow-through test on the refrigeration pipeline with nitrogen, and then carry out evacuation, filling of refrigerant, test machine, and sealing.
The second fault machine is not cooling but the compressor is running
Ordinary freezer secondary failure machine does not refrigerate, 80% is caused by irregular operation or omission of procedures, such as ice block, dirty block is the system opening time is too long, and the system is not blown through before the system is evacuated. The main reason for the dirty block is the wrong grinding method during welding or the grinding dirt enters the system. Large running noise and poor cooling are mostly caused by unclean pumping. The refrigeration difference is mostly due to insufficient or too much refrigerant charge, and some are missing the compressor discharge performance. Therefore, here is to remind the maintenance personnel to carry out each operation strictly in accordance with the regulations. It is best to blow through the system with nitrogen before the system is evacuated and replace the filter drier.
Freezer
The above article comes from the price of Ouxue freezers and freezers. For details, please log in: Freezer http://www.ox800.com
Free order hotline: 400-6300-692
No refrigeration, the compressor rotates and there is no abnormal appearance: no refrigeration, the compressor operates normally, the exposed refrigeration pipeline has no oil stains, and the freezing side of the middle door frame has no rust. Failure analysis: Most of the anti-exposure pipes leak or the compressor does not exhaust, and the other refrigeration pipes are leaky. Troubleshooting: Plug in the freezer power supply and run the compressor for 10 minutes to 20 minutes. When it continues to run, open the process nozzle of the compressor and observe the suction and exhaust conditions.
① A large amount of gas is discharged from the process nozzle, indicating that the amount of refrigerant in the system is acceptable, but the compressor does not discharge. Because the compressor process nozzle is of low pressure, it has a suction function instead of a discharge function. Unplug the power supply, weld the compressor exhaust pipe port, and then plug in the power supply to make the compressor run. Press the exhaust pipe port with your fingers. If it is easy to block, it further indicates that the compressor is not exhausted or the exhaust is poor. Replace the compressor of the same model.
②No gas is discharged from the process nozzle, and it feels to suck inward, indicating that the compressor exhaust pipe has a normal suction and exhaust function, that is, the compressor is normal. The anti-dew pipe should be pressured to 1.2MPa first to check for leaks, and then other refrigeration pipes should be pressured to check for leaks as usual. The anti-dew pipe is not used. Connect the condenser and the compressor exhaust pipe: If the condenser and other high-pressure pipelines are leaking, use soapy water to find the leak and repair the welding: If the evaporator leaks, the detachable model For repair welding, the non-removable model is equipped with an evaporator. After the refrigeration system is repaired, perform a blow-through test on the refrigeration pipeline with nitrogen, and then carry out evacuation, filling of refrigerant, test machine, and sealing.
The second fault machine is not cooling but the compressor is running
Ordinary freezer secondary failure machine does not refrigerate, 80% is caused by irregular operation or omission of procedures, such as ice block, dirty block is the system opening time is too long, and the system is not blown through before the system is evacuated. The main reason for the dirty block is the wrong grinding method during welding or the grinding dirt enters the system. Large running noise and poor cooling are mostly caused by unclean pumping. The refrigeration difference is mostly due to insufficient or too much refrigerant charge, and some are missing the compressor discharge performance. Therefore, here is to remind the maintenance personnel to carry out each operation strictly in accordance with the regulations. It is best to blow through the system with nitrogen before the system is evacuated and replace the filter drier.
Freezer
The above article comes from the price of Ouxue freezers and freezers. For details, please log in: Freezer http://www.ox800.com
Free order hotline: 400-6300-692
keywords:
Ranking of similar articles
- walk-in cooler disassembly and maintenance method
- Dragon fruit reveals ark makes pitaya ornamental fruit
- May 2011 refrigerated showcase Qingyuan Tour
- Represent the frozen watermelon fruit for storage
- Refrigerated showcase major sales walk - cooler in class
- 2012 take care of the old man from the supermarket refrigerated showcase
- Refrigerated showcase walk - in cooler energy-saving progresses steadily
- Refrigerated showcase walk - in cooler cleaner which aspects should be paid attention to
- refrigerated showcase Tip: Which fruits are not suitable for placing in the fruit refrigerated showcase
- Small convenience store owner should show how to choose the convenience stores ltd. refrigeration
- 2013 refrigerated showcase ltd. refrigeration lunar New Year holiday notice
- Air-conditioner noise?
- Commercial refrigeration evaporator embedment and production (6)
- The structure and working principle of computer-based supermarket refrigerated showcase
- The rapid growth of the supermarket walk-in cooler market in refrigeration equipment
- display cases Refrigeration failures and maintenance methods (9)
- walk-in cooler refrigeration failure and maintenance method (5)
- Walk-in cooler secondary failure unit refrigeration difference analysis (2)
- The general principle of design and layout of display cooler refrigeration system
- The air-conditioner doesn't automatically melt frost failure analysis
Latest news articles
- May 2011 refrigerated showcase Qingyuan Tour
- refrigerated showcase Refrigeration Equipment Co., Ltd. growth process
- Refrigerated showcase major sales walk - cooler in class
- Refrigerated showcase display cooler written commercial display cooler legend
- Refrigerated showcase walk - in cooler energy-saving progresses steadily
- 2012 take care of the old man from the supermarket refrigerated showcase
- refrigerated showcase Tip: Which fruits are not suitable for placing in the fruit refrigerated showcase
- Dragon fruit reveals ark makes pitaya ornamental fruit
- Watermelon fresh-keeping refrigerator can better preserve the nutrients of watermelon
- Represent the frozen watermelon fruit for storage
- Hairy crabs freezer frozen taste more fresh
- How hairy crabs fresh refrigerated showcase display cooler tell you
- Large supermarket display ark how to choose the right goods
- Small convenience store owner should show how to choose the convenience stores ltd. refrigeration
- Refrigerated showcase ltd. refrigeration has been a leader in innovation and energy saving
- In September 2012, refrigerated showcase west chung
- Refrigerated showcase walk - in cooler cleaner which aspects should be paid attention to
- Correctly use refrigerated showcase supermarket refrigerated showcase the matters needing attention
- , a refrigerated display showcase meat cooler features of the product
- Refrigerated showcase walk - in the cooler is icy